Shenzhen Mixsen Electronics Co.,Ltd. 86-185-6625-9936 sales@mixsen.com
5000PPM Co2 Detection Sensor UART Output Carbon Dioxide Level Sensor  For HVAC

5000PPM Co2 Detection Sensor UART Output Carbon Dioxide Level Sensor For HVAC

  • High Light

    5000 PPM UART Co2 Detection Sensor

    ,

    MIX6013 UART Co2 Detection Sensor

    ,

    MIX6013 UART carbon dioxide level detector

  • Target Gas
    CO2 Gas
  • Range
    400-5000PPM
  • Type
    NDIR
  • Size
    39x20x9.2mm
  • Output
    UART, PWM
  • Life
    >5 Years
  • Place of Origin
    Zhengzhou,China
  • Brand Name
    Mixsen
  • Model Number
    MIX6013
  • Minimum Order Quantity
    1
  • Packaging Details
    Inner packaging: foam cushion Outer packaging: carton
  • Delivery Time
    within 3 working days after payment
  • Supply Ability
    10,000/day

5000PPM Co2 Detection Sensor UART Output Carbon Dioxide Level Sensor For HVAC

400-5000PPM NDIR Carbon Dioxide(CO2) Gas Detection Sensor For HVAC System

 

Principle Introduction:

 

Mix6013 / mix6013 a CO2 gas sensor (infrared CO2 sensor) is a general intelligent small sensor, which uses non dispersive infrared (NDIR) principle to detect CO2 in the air. It has good selectivity, no oxygen dependence and long service life. Built in temperature compensation; At the same time with serial output, analog output and PWM output, easy to use. The sensor is a high-performance sensor which combines the mature infrared absorption gas detection technology with the design of precise optical path and excellent circuit.

 

Feature:

 

The gas chamber is treated with gold plating to prevent water and corrosion
High sensitivity and low power consumption
Excellent stability and long service life

 

Application:

 

HVAC and refrigeration equipment, air quality monitoring equipment, fresh air system, air purification equipment, smart home

 

Technical Parameters :

 

 

Item Specification
Measurement Range 400~2000ppm(Other range available)
Operating Principle Non-dispersive infrared(NDIR)
Power Supply 4.5~5.5V DC
Operating Current 120mA peak, 20mA average
Accuracy ±(50ppm+5% of reading)
Warm Up Time 3 minutes
Response Time T90 < 120 seconds
Time Between Detection 2 seconds
Operating Conditions 050/090%Rh(No condensation)
Storage Conditions - 20~60℃/0~90%Rh(No condensation)
UART (TTL interface level 3.3V)
Communication Interface PWM
Vout (Analog output interface)
Size 39 X 20 X 9.2 (mm)
Weight Approx.5g
Using Life >5 years